16. EVACUATE
When the soft key "Evacuate" is pressed, all outputs that are programmed for sounders (type "Alarm devices" and "Alarm devices
for evacuation"), will be collectively turned ON (steady). This is indicated in the LCD:
EBL512 G3
Evacuate in progress
yyyy-mm-dd hh:mm
Alternatively, the same is the result when an input programmed as "Evacuate" is activated. One input per c.i.e.
Also sounders programmed with type "Alarm devices for evacuation" will be disabled by H2/B4.
The sounders will remain turned ON until they are turned OFF by pressing the soft key "Evacuate off" or alternatively when the
programmable input is de-activated.
Outputs type "Alarm devices": The alarm devices (sounders) will always be activated steady (sound continuously) irrespective of
the fact that the outputs can be set to anything else for fire alarm (e.g. intermittent).
Addressable alarm devices: The alarm devices (sounders) will always be activated according to the setting in; High priority /
Output signal period