8.1.5.
USER LEVEL 3A
After the door has been opened with the fire brigade key ("Door open" symbol
personnel have access to level 2A and after log on as "Service personnel" (level 3A), access to all menus, i.e. like level 2C and also
to the following menus:
Same menus as in access level 2C plus the following:
H5 Service
•
A1 Calibration of supervised outputs
•
A2 Sensitive fault detection mode
•
A3 Service mode for COM-loop
•
A4 Display current consumption in control unit
•
A5 Display current consumption on COM-loop
•
A6 Display statistics for communication
•
A7 Activate address setting mode for DU
•
A8 Setup wireless detectors
•
A9 SSD information
H8 Maintenance
•
S1 Dis- / Re-connect loop / zone line input
•
S2 Acknowledge SERVICE signal
•
S3 Clear weekly average
•
S4 Test of alarm devices
•
S5 Safe shut down of control unit
•
S6 Activate address in alarm mode
•
S7 Synchronize the control units
•
S8 Activate / Reset outputs
H10 Change password (In this case for "Service personnel".)
8.1.6.
ACCESS LEVEL 3B
Used by Service / maintenance / commissioning engineers when a PC (i.e. EBLWin) is to be connected to EBL512 G3 for backup
(upload), download of site specific data (SSD) and/or download of software. EBLWin require an EBLWin key (5094) to be plugged in
the PC.
8.1.7.
ACCESS LEVEL 4
Used by manufacturer or by personnel authorised by the manufacturer for re-initialisation (reset) of the alarm counter, change soft-
ware configurations, on-line status checking, etc. An EBLWin key (5094)
is required to be plugged in the PC.
in the symbol area), the service / maintenance