Silence Buzzer - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

13. SILENCE BUZZER

The buzzer in the control unit will sound for:
Fire alarm (0.4 / 0.4 sec.)
Co-incidence alarm (2-zone or 2-unit dependent fire alarm): When only one zone or one zone / address (alarm point) is in alarm
status (0.8 / 5 sec.)
Pre-warning (0.8 / 5 sec.)
Quiet alarm (0.8 / 5 sec.)
Fault (continuous)
Disablements and Faults (1 sec. directly after the door to the c.i.e. is closed.)
Activated interlocking input (0.8 / 0.8 sec.), if this option is selected via EBLWin.
Activated technical warning (0.5 / 10 sec.), if this option is selected via EBLWin.
PRESS "SILENCE BUZZER" TO SILENCE THE BUZZER
In case of a new alarm (pre-warning, co-incidence alarm, and so on) or if the push button "Silence buzzer" is pressed again, the
buzzer will automatically sound again.
SILENCE BUZZER BY OPEN DOOR
In EBLWin the function "Silence Buzzer by Door Switch" can be selected. The buzzer will then be turned off as long as the control
unit door is open. (This function is a violation to the EN54-2 standard.)
EBL512 G3 C.I.E. TYPE NO. 5001
This unit has no front and no built-in buzzer.
31

Advertisement

Table of Contents
loading

Table of Contents