EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

35.3. DISABLE / RE-ENABLE INTERLOCKING OUTPUT (H9/C3)

Interlocking outputs (Type = Interlocking) can be individually disabled via this menu (and collectively via menu H2/B3). The "In-
terlocking Combination" (Area / Point) is to be entered to disable the output. Up to 100 interlocking outputs can be disabled in the
whole system. Disabled interlocking outputs are listed in menu H4/U1 from which it is also possible to get a print-out. The LED Fault
/ Disablements "General disablements" is also indicating one or more disabled interlocking outputs.
a) Log on to the c.i.e.
b) Navigate to menu C3.
c) Write the area number and address and press
d) Press
to disable the output. Indicated by "√" and a beep. The loop will directly be shown in the Re-connect list.
Disable
Interlocking output area: 001 point: 01
-- Re-enable list (1) ----------------------------------------
------
Interlocking output area: 001 point: 01
RE-ENABLE
e) Use the soft key
- Disable
- Re-enable list
f) Select an item in the re-enable list and press
g) To exit the menu press ESC .
to toggle between
.
. Re- enabled output will disappear from the list, indicated with a beep.