19. ALARM RESET
19.1. PRE-WARNING RESET
Pre-warning is automatically reset.
19.2. FIRE ALARM RESET
The detectors having activated fire alarm shall, after reset, be inspected, tested and replaced when re-
quired. One of the following alarm reset alternatives is valid. This is selected via EBLWin. "All" is default.
19.2.1. ALL
All activated fire alarms (alarm points / zones) will be reset by pressing "Reset" once. (This is in accordance with the EN54-2
standard).
The push button has to be pressed for min. 0.5 sec.
When all fire alarms are reset, LEDs "Fire" and "Alarms queued" are turned off. If there are other conditions (e.g. a fault condition)
the corresponding information will be shown (for example. a fault message), for the priority order see section
on page 18.
PRIORITY ORDER
All outputs (for fire alarm) are reset.
If a key cabinet is installed, the key (to the building) has to be put back into the key cabinet within 5 minutes. If not, a fault will be
generated and a fault message will be shown in the display, see section
When "Single" or "Single with automatic disablement" is used, all alarms can be reset by pressing "Reset"
and approx. 0.1 sec. later also press "Enter" and hold them pressed for > 0.5 sec.
19.6. KEY CABINET ALARM RESET
50
5.4. INFORMATION
on page 53.