EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
Supervised (EN54-13):
x=0 (S0): Short circuit/break on the connected cable/ equipment
x=1 (S1): Short circuit/break on the connected cable/ equipment
x=2 (S2): Short circuit/break on the connected cable/ equipment
x=3 (S3): Short circuit/break on the connected cable/ equipment
Fuse T500mA L 250V
Connected equipment might be "stolen".
End-of-line device 4472 missing
FAULT: Supervised output x expansion board
x, control unit xx
A fault on the supervised output x on the expansion board 4583 with address x, in control unit no. xx.
If the output is programmed for sounders (type Alarm devices), it is also indicated by LED Fault / Disablements "Alarm devices"
blinking.
If the output is programmed for fire brigade tx (type Routing equipment), it is also indicated by LED Fault / Disablements "Fire
brigade tx" blinking.
Calibration not performed via menu H5/A1.
Short-circuit / break on the connected cable / equipment.
Blown fuse F1 (Output 0) or F2 (Output 1) on the 4583 board. Fuse T200mA L 250V (TR5).
Connected equipment might be "missing".
End-of-line resistor(s) missing or not correct value, (1-5 resistors 33kΩ).
The calibrated value has to be in the range 4.7 kΩ - 40 kΩ.
FAULT: Supervised output x,
technical number xxxxxx
This fault message is valid for a COM loop output unit 3364 output or 4464 board output.
If the output is programmed for sounders (type Alarm devices), it is also indicated by LED Fault / Disablements "Alarm devices"
blinking.
If the output is programmed for fire brigade tx (type Routing equipment), it is also indicated by LED Fault / Disablements "Fire
brigade tx" blinking.
Calibration not performed via menu H5/A1.(Valid for 3364 only)
Short-circuit / break on the connected cable / equipment.
Connected equipment might be "stolen".
End-of-line capacitor(s) missing or not correct value, 1-5 capacitors (470 nF). (Valid for 3364 only)
End-of-line device 4472, or end-of-line resistor, is missing (Valid for 4464 only)
The calibrated value has to be in the range 470 nF – 5 x 470 nF (2350 nF). (Valid for 3364 only)
73