12. DISABLE OR RE-ENABLE ALARM DEVICES

Outputs programmed for sounders can be collectively disabled for all control units during Fire alarm or Alert Annunciation alarm.
This is done via menu H2/B4. The disablement is indicated by LED Fault / Disablements "General disablements" and "Alarm devic-
es", which are steady ON.
In case of a fire, the sounders will remain disabled, which means the alarm devices will not sound until they are re-enabled again via
menu H2/B4.
Outputs of type "Alarm devices" cannot be individually disabled, not even via menu H2/B2 Disable or
Re-enable Output. See also chapter 34.4. TEST OF ALARM DEVICES (H8/S4) on page 119. All outputs of type
"Alarm device" for a specified control unit or all control units, can be activated for an alarm device test.
Also sounders programmed with type "Alarm devices for evacuation" will be disabled by H2/B4.