Setup Wireless Detectors (H5/A8) - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

31.8. SETUP WIRELESS DETECTORS (H5/A8)

This function can be used by commissioning / service engineer to set a Base station for wireless units (4620) to one of the following
modes:
Register - in order to register one or more wireless units 4611 / 4614 / 4645 to the Base station.
Unregister - in order to unregister one or more wireless units 4611 / 4614 / 4645 from the Base station.
Install - in order to change the communication from normally every 2nd minute to every 5th second, to be used during commission-
ing, and so on.
To set the Base station to any of the modes above the Base station must be in a "Normal state", i.e. not set
to any of the modes. For example, a Base station set to e.g. "Register" mode must be set back to "Normal
state" before it can be set to any other mode.
For more information, see Technical description MEW01764.
a) Log on to the c.i.e.
b) Navigate to menu A8.
c) Write the technical number for the base station.
d) Press
or
to scroll between:
- Register
- Unregister
- Install
e) Press
to select a state.
SET TO NORMAL STATE
f) Use the soft key
- Set base station mode
- Base station mode
g) Select the base station with the correct technical number in the list and press
state. The Base station will disappear from the list, indicated with a beep.
h) To exit the menu press ESC.
The Base station must be set back to the "Normal state" for the wireless detectors to function normally.
to toggle between:
. The base station is now back in Normal