Select Unit On Com-Loop To Use For Trigging (H5/A8) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
28.9
Action
"Access"
Scroll to menu A8
"A"
"A"
or
"1", "A"
"A"
"Return"
Rev: -
Select unit on COM-loop to use for trigging
(H5/A8)
NOTE! This menu is not valid for an EBL512 G3 control unit in a
mixed system.
This function is used by service engineer and by R&D for
troubleshooting.
112
On the pin
respectively you will get a pulse to trig an oscilloscope
etc.
COM loop
Main board 1556, JP2, "upper" pin: Each unit not giving a correct
answer.
Main board 1556, JP2, "lower" pin: A specific unit is being polled.
BS4 loop
Autronica interface board 1584 (in the c.i.e.), BY3, "left" pin: A
specific unit is being polled.
Autronica interface board 1584, BY3, "right" pin: 0 V.
(BS4 board = Autronica interface board 1584)
Text in display
Select unit on COM-/BS4-loop to use for
trigging
Select type of loop: 0 (0=COM, 1=BS4)
CU: 00 Loop: 0 Address: 000
CU 00, BS4-Board 0, Loop: 0, Address: 00
Select type of loop: 0 (0=COM, 1=BS4)
Select unit on COM-/BS4-loop to use for
trigging
112
The pin might be removed from the p.c.b.
Operating Instructions Fire alarm system EBL512, V2.7.x
ACCEPT? A8
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? A8
134
Comments
According to chapter
"Access code for service
(H5)", see page 126.
Select type of loop. Press
"A" to accept.
Write control unit number,
(board number; 0-3), loop
number and address. Press
"A" to accept.
Select type of loop. Press
"A" to accept or press
"Return" to menu A8..
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.