Fault Acknowledge - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
17.2
Operating Instructions Fire alarm system EBL512, V2.7.x

Fault acknowledge

The LEDs "Fault tx activated" (L11) and "General fault" (L7) are
67
turned ON
.
(LEDs "Fault / Disablements Alarm devices" (L13), "System fault"
(L14) and/or "Fault / Disablements Fire brigade tx" (L15) might be
turned ON as well.
Output(s) for routing equipment (Fault tx) is (are) activated.
Output(s) for general fault is (are) activated.
Output(s) for general charge fault might be activated.
A fault message, date and time is shown in the EBL512 display(s).
After the time might be shown
fault is generated in the system.
After the time might be shown
Serviced
"
serviced / corrected.
are set to be "Not latched".
Login, according to chapter "Access", page 92.
Use menu H6 (access level 2) for fault acknowledge, see
chapter "Acknowledge FAULTS (H6)", page 138. Menu H6 is
a list showing a maximum of 200 faults (not acknowledged
faults and/or acknowledged but not corrected faults). The first
fault in the list is the most recent fault. When a fault is
acknowledged and corrected it will be removed from the list
and a new fault can be shown. Corrected faults are shown in
the event log (menu H4/U7).
All faults have to be individually acknowledged one by one
(push button "Fault acknowledge" (P6). Use  or  keys to
scroll.
If a fault has been corrected before it has been acknowledged,
Serviced
"
the text
be acknowledged.
When a fault is corrected and acknowledged, it will disappear
from the list (H6).
When all faults have been acknowledged, output(s) for routing
equipment (Fault tx) is (are) reset (i.e. the LED "Fault tx
activated" (L11) will be turned off).
As long as there are faults (i.e. not acknowledged faults and/or
acknowledged but not corrected faults) the LED "General fault"
(L7) will be lit and general fault (and maybe general charge
fault) output(s) are activated.
67
Indicating that output for routing equipment (Fault tx) is activated.
68
Via Win512 version 2.7.x the faults can be set to be not latched.
Corrected faults will in this case automatically disappear from the list without
being acknowledged before.
76
More faults
"
"
Serviced
"
"
= the fault is already
"
will never be shown if the faults
"
is added after the time.
= more than one
68
It still has to