Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
31.4
Action
"Access"
Scroll to menu S3.
"A"
"A"
Depending on the
chosen type, 0, 1, 2 or
3, the following will be
shown:
"A"
"Return"
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x

Re-connect loop (H8/S3)

Disconnected (disabled) loops / zone lines (via menu H8/S2) are
indicated by LED "Disablements" and listed in menu H4/U1.
NOTE! When you re-connect a COM loop all the statistics shown in
menu H5/A7 will be erased and set to "0".
Text in display
Re-connect loop
Re-connect type: 0 (0=COM, 1=BS4,
2=DET8, 3=Loop Unit)
Re-connect COM-Loop: 0, CU: 00
Re-connect BS4-Loop: 0, Board: 0, CU: 00
Re-connect DET8-input: 0, Board: 0,
CU: 00
Re-connect input technical no.: 000000
Re-connect type: 0 (0=COM, 1=BS4,
2=DET8, 3=Loop Unit)
Re-connect loop
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
144
Comments
According to chapter
"Access code for
maintenance", see page
141.
S3
Press:
"0"=COM loop
"1"=BS4 loop
"2"=Expansion board 1580
"3"=Addr. zone interface
2226 / 2335
3361 (MIO).
Press "A" to accept.
Write the required
numbers. Press "A" to
accept.
Continue to re-connect or
press "Return" to menu S2.
LED "Disablements" will
be turned off if there are
no other disablements in
the system.
Scroll or press "Return" to
S3
return to menu H8. Scroll
or press "Return" to log
off.