Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
The unit is programmed as another type of unit than the SSD says or
fault in the unit.
FAULT: EPU xx, CU xx
EPU=1728
The unit is programmed as another type of unit than the SSD says or
fault in the unit.
FAULT: Expansion board x, CU xx
This is valid for the expansion boards 4580, 4581 & 4583, i.e. no. x,
mounted in the control unit no. xx.
There is some internal fault on the board, which has to be replaced.
FAULT: Expansion board x, loop x, CU xx
This is valid for the I/O Matrix board (4582) no. x, connected on
COM loop x in the control unit no. xx.
There is some internal fault on the board.
FAULT: External FBP x, board x, CU xx
The control unit (i.e. the 1582 board) cannot communicate with the
ext. FBP (or data converter).
Check the connections.
Check the cable (break?).
Check the address DIL-Switch in the ext. FBP. Is correct
address set?
Several ext. FBPs have the same address.
Faulty ext. FBP.
FAULT: External fuses, control unit xx
The fault is to be found in the external power supply (blown fuses,
etc.).
FAULT: External power supply, CU xx
The fault is to be found in the external power supply connected to
64