28.8
Action
"Access"
Scroll to menu A7
"A"
"A"
"A"
Rev: -

Display statistics for COM-loop (H5/A7)

The statistics can be used during commissioning, service, etc.
Pollings are the number of pollings ("questions") sent out by the
control unit to the units connected on the COM loop.
Parity are the received number of parity faults and % (faults in
relation to pollings).
Bit are the received number of bit faults and % (faults in relation to
pollings).
Answer are the received number of answer faults / no answers and %
(faults in relation to pollings).
The Parity, Bit and Answer values shall normally be "0" or as close to
"0" as possible. If not, there are some communication problems that
have to be investigated. Check the COM loop, connections and the
loop units.
All values are set to "0" after restart and/or after re-connection of
COM loop (menu H8/S3).
Text in display
Display statistics for COM-loop
For which CU 00 and COM-loop 0 shall
statistics be displayed?
Wait......
No reply from control unit.....
Pollings 1234567
Bit 000000 00.0%
Display statistics for COM-loop
111
Note! The values are not live updated, i.e. the shown values were valid
when "A" was pressed in menu A7. To see the actual values, press "A" to
menu A7, press "A" and write control unit and loop number again and press
"A". Normally is only the value "Pollings" changed.
Operating Instructions Fire alarm system EBL512, V2.7.x
ACCEPT? A7
ACCEPT?
Parity 000000 00.0%
Answer 000000 00.0%
ACCEPT? A7
133
Comments
According to chapter
"Access code for service
(H5)", see page 126.
Write control unit and loop
number. Press "A" to
accept.
If the control unit don't
exist or don't answer, this
message will be shown.
111
Press "A" to menu A7.
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.