Panasonic Electric Works Nordic AB
MEW01349
28.6
Action
"Menu"
"↵ "
Scroll to menu A5
"↵ "
"↵ "
"↵ " or "ESC"
Rev: -
Display current consumption COM-loop
(H5/A5)
The resolution is not very high, i.e. the displayed values give only a
rough idea of the current consumption.
The current consumption (an average value) for each COM loop can
be displayed.
NOTE! No or very small current consumption can not be presented
correctly / precisely.
Text in display
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A5 Display current consumption on COM-loop
Display current consumption on
COM-loop: 0, control unit: 00
(press ↵)
Wait......
No reply from control unit.....
Current consumption on COM-loop: 0 control unit
00 is xxxx mA
A5 Display current consumption on COM-loop
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
122
Comments
According to chapter
"Access code for service /
maintenance (H5 and
H8)", see page 116.
Write loop number and
control unit number and
↵
press "
".
If the control unit don't
exist or don't answer.
The current consumption
accuracy is ±5 mA.
Scroll to another menu or
press "ESC".