Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Acknowledge SERVICE signal (H8/S3)

When SERVICE signal is generated in the system, following symbol
is shown in the display's symbol area:
activating SERVICE signal (H4/U5)", page 111.
When service signal from a sensor is acknowledged, the sensor is
given a default sensor value (same as for a new / clean sensor), i.e.
first replace the sensor and then acknowledge the service signal as
soon as possible.
acknowledge) will be calculated within one hour, then each week.
NOTE! If a sensor is replaced without having generated service
signal, it has to be reset to the default sensor value via menu H8/S4,
page 134.
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
S3 Acknowledge SERVICE signal
Sensor : xxx-xx
(Technical number xxxxxx) needs service
Sensor : yyy-yy
(Technical number yyyyyy) needs service
Sensor : zzz-zz
(Technical number zzzzzz) needs service
The first week average sensor value (after
132
See also chapter "Sensors
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
This is a dynamic list in
which you can scroll. The
most recent service signal /
sensor is on top of the list.
Use "▼" or "▲" to select
(t
a sensor
he selected
sensor has a border).
"↵ "
Press
to acknowledge
.
the sensor