Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
30.5
Action
"Access"
Scroll to menu S4.
"A"
"Fault acknowledge"
"Return"
Rev: 1

Acknowledge SERVICE signal (H8/S4)

See chapter "Sensors activating SERVICE signal (H4/U6)", page 100.
When service signal from a sensor is acknowledged, the sensor is
given a default sensor value (for a new / clean sensor), i.e. first
replace the sensor, then acknowledge the service signal as soon as
possible.
NOTE! If a sensor is replaced without activating service signal, it has
to be reset to the default sensor value, see chapter "Clear weekly
average (H8/S5)", page 124.
Text in display
Acknowledge SERVICE signal
Sensor : xxxxxx needs service
NOTE! The list order in this menu is as follows:
a) Technical number order in the control unit this menu is
opened.
b) Technical number order in the rest of the system.
The service signal for that sensor is now acknowledged and
the next sensor will be shown in the display.
Sensor : yyyyyy needs service
Acknowledge SERVICE signal
LED "Service" (L12) will be turned off when all sensors have been
acknowledged.
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? S4
ACCEPT? S4
123
Comments
According to chapter
"Access code for
maintenance", see page
119.
If there are no sensors to
acknowledge, menu S4
L
will be shown again.
L = a list in which you can
scroll. If it is the correct
sensor to acknowledge,
press "Fault acknowledge".
If not, scroll or write the
wanted sensor and press
"Fault acknowledge" or
press "Return" to S4.
If more service signal
acknowledgements shall
be done, continue like
above. If not, press
L
"Return" to menu S4.
Scroll or press "Return" to
menu H8. Scroll or press
"Return" to log off.