Operating Instructions Fire alarm system EBL512 V2.3.x
FAULT:Sh-circ. loop x, CU xx, ASF5<->CU
FAULT:Sh-circ. loop x, CU xx, ASF4<->CU
FAULT:Sh-circ. loop x, CU xx, ASF3<->CU
FAULT:Sh-circ. loop x, CU xx, ASF2<->CU
FAULT:Sh-circ. loop x, CU xx, ASF1<->CU
FAULT:Sh-circ. loop x, CU xx, ASF0<->CU
Short circuit on the COM loop "x" (one or more short circuit
isolators 2370, ASF, are connected on the loop). Check the
specified and isolated segment on the loop (e.g. CU <->ASF0 =
between the control unit and short circuit isolator no. 0). Each 10
minute is an attempt made to re-enable the isolated segment again.
FAULT: Site specific data (SSD), CU xx
Some external influence (or after download) has caused a checksum
fault in the (from Win512) downloaded Site Specific Data (SSD). (An
SSD download is required.). This is very serious. Call for service
personnel/engineer immediately.
FAULT: SSD, AAU xx, 1587-board x, CU xx
AAU=1735 / 1736
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: SSD, EPU xx, 1587-board x, CU xx
EPU=1728
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: SSD, FBP xx, 1587-board x, CU xx
FBP=1826 / 1828
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Supervised output x, CU xx
If the output is programmed for sounders (type 3 = alarm devices), it
is also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.