Ebl512 Settings Download; Control Units In A Tlon Network - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
Rev: 1
20
20.1
Operating Instructions Fire alarm system EBL512 V2.3.x

EBL512 settings download

EBL512 settings are normally factory downloaded before the delivery.
It is however, possible to download the following on site:
The number of addresses (max. loop units)
Serial number (normally not changed)
Date (normally not changed)
Adhesive type (Type 1 = "old", Type 2 = "new"; acc. to EN54)
If you wish to download new EBL512 settings, a PC and Win512 are
used.
Before download, the PC has to be connected to the "D"
connector J1 in the control unit main board 1556 in question.
1. Start Win512. In the "Tools" menu open the "EBL512 settings"
dialog box.
2. Set the c.i.e. in "Bootstrap mode", i.e. set jumper "JP1 (BOOT)" in
position on the main board 1556.
3. Do a reset/restart, i.e. set jumper "JP4 (RESET)" in position
momentarily (approx. 1 second).
4. The buzzer will now sound intermittent and LED "LD101" starts
64
blinking
, indicating that the control unit is in "Bootstrap mode".
5. In the "Win512 settings" dialog box, click "Read". The buzzer
will be silenced, the actual settings shown and in the Win512 log
view will be shown: "System information has been uploaded."
6. Write the new settings in the fields respectively.
7. Do like 3 & 4 above. Click "Download". The buzzer will be
silenced and a "Win512" box will be displayed. Click "OK".
NOTE! If "Max. loop units" are changed, a "Please enter your
password" dialog box will be shown.
8. When the download is ready, in the Win512 log view it will be
shown: " System information has been downloaded".
9. Read, see 3, 4 & 5 above, to verify the new settings.
10. Remove jumper "JP1 (BOOT)". Do a reset/restart, see 3 above.
Regarding the reset/restart, see chapter "Restart", page 69.
Follow the same procedure in each control unit.

Control Units in a TLON network

All control units connected to a TLON network have the same
convention (via the SSD download) but the number of addresses
(max. loop units) and the language can vary if required.
65
To change the "Max. loop units", a separate download password is
required. This password is in conjunction with a "Key" (eight digits) and is
available from the producer if you are authorized. The Key is shown in
Win512 and the procedure is described in the Win512 help.
68
65
65

Advertisement

Table of Contents
loading

Table of Contents