Change Access Code For Pc-Communication (H5/A10) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
27.11
Action
"Access"
Scroll to menu A10
"A"
Rev: 1
Change access code for PC-
communication (H5/A10)
As a protection against unauthorised personnel programming the
system (via Win512), an access code (level 5) for PC-connection is
required. For security reasons, the default code should be changed.
NOTE! This code requires eight (8) digits.
Text in display
Change access code for PC-communication
Access code: _
New code: ********
Incorrect access code, NO change
Change access code for PC-communication
NOTE! After change of access code it is recommended do a "Safe
shutdown of the control unit" (see menu H8/S8). This will save the
SSW data (e.g. the new code) in a Flash ROM (see page 69).
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? A10
Verify: ********
ACCEPT? A10
114
Comments
According to chapter
"Access code for service
(H5)", see page 104.
The digits are replaced
(********) in the display.
The code was not correct.
Try again.
The code was correct and
is now changed to the new
code. Scroll or press
"Return" to H5. Scroll or
press "Return" to log off.