19.1
Operating Instructions Fire alarm system EBL512 V2.3.x
New system program (S/W) version
download
The latest version of the EBL512 S/W (system program) is factory
downloaded before the delivery. Due to continual development and
improvement, different S/W versions can be found.
The valid S/W version can be read in menu H3 or via Win512. New
S/W can on site be downloaded via Win512. See also the Win512
help chapter (help topic) "Download Software".
New S/W for the 1728, 1735 / 1736 & 1826 / 1828 units (connected to
an Ext. FBP/DU interface board 1587) can also on site be downloaded
via Win512. See the Win512 help chapter (help topic) "Display unit
menu" and the "Technical Description" for the unit respectively.

A single control unit (c.i.e.)

A single c.i.e. must not have a TLON connection board 1590
62
mounted.
To download a new software (system program) version, a PC and
Win512 are used. Before download, the PC has to be connected to
the "D" connector J1 in the control unit main board 1556 in question.
1. Start Win512.
software" dialog box and do the required settings, e.g. the path for
the S/W (.BIN) file and/or the language (.SST) file
forget to mark the checkbox respectively.
2. Set the c.i.e. in "Bootstrap mode", i.e. set jumper "JP1 (BOOT)" in
position on the main board 1556.
3. Do a reset/restart, i.e. set jumper "JP4 (RESET)" in position
momentarily (approx. 1 second).
4. The buzzer will now sound intermittent and LED "LD101" starts
64
blinking
, indicating that the control unit is in "Bootstrap mode".
5. Start the downloading (click "Download"). The buzzer will now
be silenced and LED "LD101" is turned on (continuously).
62
When a c.i.e. has a TLON connection board 1590 mounted, it is expected
to be one c.i.e. in a TLON network and TLON network programming is
required.
63
Normally only download of the new S/W file is required. If, after the
download and restart, a message is displayed that a new text (language) file
also is required, download it as well.
64
Also the LED "System fault" (L14) starts blinking.
66
In the "Tools" menu open the "Download
63
. Do not