Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
Rev: 1
26.5.1
Operating Instructions Fire alarm system EBL512 V2.3.x
Algorithm
Normal sensitivity & Normal detection (15 s)
High sensitivity & Normal detection (15 s)
Low sensitivity & Normal detection (15 s)
Normal sensitivity & Slow detection (35 s)
High sensitivity & Slow detection (35 s)
Low sensitivity & Slow detection (35 s)
Heat algorithm, Class A1
Heat algorithm, Class A2 (S)
Heat algorithm, Class B (S)
Decision algorithm
Default is N-15 and A1 respectively.

Reset of a week average sensor value

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
set to the default value otherwise the new / clean sensor will inherit
the old sensor's value. It is possible to clear the week average sensor
value for each sensor individually, see chapter "Clear weekly average
(H8/S5)", page 124. See also chapter "Acknowledge SERVICE signal
(H8/S4)", page 123.
NOTE! Authorised service personnel only, must do the reset to
default value. Used incorrectly it can cause nuisance fire alarms.
77
If some other short name is wanted, it can be changed in Win512. Up to
six characters can be used. In the DBI (Danish) convention, up to five
characters.
78
Low sensitivity and/or slow detection (35 s) might not fulfil the EN54-7
specifications.
79
Analog multi detector 3316 only.
94
Short name
77
(nnnnnn)
N-15
H-15
78
L-15
78
N-35
78
H-35
78
L-35
A1
A2
B
79
Dec