Fault Acknowledge - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
Rev: 1
16.2
Operating Instructions Fire alarm system EBL512 V2.3.x

Fault acknowledge

The LEDs "Fault tx activated" (L11) and "General fault" (L7) are
55
turned ON
.
(LEDs "Fault / Disablements Alarm devices" (L13), "System fault"
(L14) and/or "Fault / Disablements Fire brigade tx" (L15) might be
turned ON as well.
Output(s) for routing equipment (Fault tx) is (are) activated.
Output(s) for general fault is (are) activated.
Output(s) for general charge fault might be activated.
A fault message, date and time are shown in the control unit(s)
display.
After the time might be shown
fault is generated in the system..
If Fault latching is selected in Win512, after the time might be shown
= the fault is already corrected.
"Serviced"
• Login, according to chapter "Access", page 72.
• Use menu H6 (access level 2) for fault acknowledge, see
chapter "Acknowledge FAULTS (H6)", page 116. Menu H6
is a list showing a maximum of 200 faults (not acknow-
ledged faults and/or acknowledged but not corrected faults).
The first fault in the list is the most recent fault. When a
fault is acknowledged and corrected it will be removed from
the list and a new fault can be shown. Corrected faults are
shown in the event log (menu H4/U7).
• All faults have to be individually acknowledged one by one
(push button "Fault acknowledge" (P6). Use ↑ or ↓ keys to
scroll.
• If a fault has been corrected before it has been
acknowledged, the text
time. It still has to be acknowledged.
• When a fault is corrected and acknowledged, it will
disappear from the list (H6).
• When all faults have been acknowledged, output(s) for
routing equipment (Fault tx) is (are) reset (i.e. the LED
"Fault tx activated" (L11) will be turned off).
• As long as there are faults (not acknowledged faults and/or
acknowledged but not corrected faults) the LED "General
fault" (L7) will be lit and general fault (and mightbe general
charge fault) output(s) are activated.
55
Indicating that output for routing equipment (Fault tx) is activated.
60
= more than one
"More faults"
is added after the
"Serviced"

Advertisement

Table of Contents
loading

Table of Contents