Synchronize The Control Units (H8/S10) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
30.11
Action
"Access"
Scroll to menu S10.
"A"
"1", "A"
"A"
Rev: 1

Synchronize the control units (H8/S10)

Synchronization can also be done via Win512.
The control units have to be synchronized when:
The following fault message is shown:
FAULT: CU xx has wrong information
See chapter (help topic) "View Faults" in the Win512 help.
During the synchronization there will be displayed information for the
control unit respectively. The information is shown on the second row
in positions 1 to 30, i.e. one position for each control unit 00-29.
- = Synchronization not started.
X and ? alternating = Synchronization in progress for CU = X (X is
the last digit in the control unit number, e.g. 8 for CU no. 18 and 28).
+ = Synchronization completed
<Blank> = There is no control unit with that number in the system.
Text in display
Synchronize the control units
Shall synchronization be started? 0
(1 = Yes, 0 = No)
Synchronization in progress...
0+--4+?78+??+-4
Synchronization completed MM-DD
+++++++++++++++
95
If the CU restarts in conjunction with this fault, the synchronization will
start automatically otherwise it has to be started via this menu.
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT?
ACCEPT?
+8+0?2?+?+78+ ACCEPT?
HH:MM
+++++++++++++ ACCEPT?
130
95
Comments
According to chapter
"Access code for
maintenance", see page
119.
S10
Press "1" and "A" to start
the synchronisation or
press "A" to go directly to
the field "Synchronization
completed" or press
"Return" to menu S10.
During the synchronization
the information on each
position (on row 2) is
changing all the time. 28
CUs are shown in the
example (i.e. 15 & 16 are
not programmed). Press
"A" to continue.
Month (MM), day (DD)
and time for the latest
completed synchronization

Advertisement