Disable / Re-enable all control, exting. and
ventilation outputs (H2/B8)
73
Outputs
programmed as type 0 = control (general), type 1 = fire
ventilation and/or type 2 = extinguishing system
at the same time. Disabled control output means that even if the
control expression (trigger condition) for the output respectively is
fulfilled, the output will not be activated.
Disabled control outputs are indicated by LED "Disablements" (L8)
and is shown in menu H4/U1.
The outputs in one or more control units can be disabled or the outputs
in all control units.
The outputs will be disabled until re-enabled again (via this menu).
Text in display
Disable or re-enable
Disable zone
Disable / Re-enable all control, exting.
and ventilation outputs
Disable (=0) or Re-enable (=1) outputs?1
CU 99 (99 = All)
Disable / Re-enable all control, exting.
and ventilation outputs
73
Including Addressable siren 3377 and Addressable sounder base 3378.
74
Also the "Extinguish equipment output" on the German FBP interface
board 1583.
75
NOTE! Outputs disabled for a specific control unit (e.g. CU 03) can not
be collectively re-enabled via CU 99. You have to re-enable the outputs for
the specific control unit(s), e.g. CU 03.
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B8
ACCEPT?
ACCEPT? B8
85
74
can be disabled all
Comments
According to chapter
"Access", see page 72.
Press "1" or "0", write the
CU number (or "99" for all
75
CUs)
and press "A" to
accept.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.