Operating Instructions Fire alarm system EBL512 V2.3.x
FAULT: Sensor techn. no. xxxxxx
• The sensor 22xx / 23xx is removed from its sensor base
2210 / 2312.
• Faulty sensor.
• The analog detector 33xx / 43xx (in NORMAL mode): The
built-in self verification function has reported a fault status.
(Detector removed from its base generates FAULT: No
reply .....)
FAULT: Short-circuit COM-loop x, CU xx
Short circuit on COM loop "x" (short circuit isolator is not
connected on the loop). Check the loop
NOTE! As long as there is a short circuit, the COM loop is disabled.
th
Each 10
minute is an attempt made to re-enable the loop again.
FAULT:Sh-circ input x,1580 board x,CU xx
(8 zones expansion board, DET8)
This is indicating short-circuit on input x (zone line) on the 1580
board. The wires (cable) might have been damaged.
NOTE! As long as there is a short circuit, the zone is disabled. Each
minute is an attempt made to re-enable the zone again.
FAULT: Short circ. loop x, BS4 x, CU xx
(1584 Autronica interface board, BS4)
Short circuit, or current consumption >167mA, on the BS4 loop
(short circuit isolator is not connected on the loop). Check the loop
NOTE! As long as there is a short circuit, the BS4 loop is disabled.
th
Each 10
minute is an attempt made to re-enable the loop again.
FAULT:Sh-circ loop x, CU xx, CU <->ASF0
FAULT:Sh-circ loop x, CU xx,ASF0<->ASF1
FAULT:Sh-circ loop x, CU xx,ASF1<->ASF2
FAULT:Sh-circ loop x, CU xx,ASF2<->ASF3
FAULT:Sh-circ loop x, CU xx,ASF3<->ASF4
FAULT:Sh-circ loop x, CU xx,ASF4<->ASF5
FAULT:Sh-circ loop x, CU xx,ASF5<->ASF6
FAULT:Sh-circ loop x, CU xx,ASF6<->ASF7
FAULT:Sh-circ. loop x, CU xx, ASF7<->CU
FAULT:Sh-circ. loop x, CU xx, ASF6<->CU