Operating Instructions Fire alarm system EBL512 V2.3.x

Programming (SSD download)

The PC program Win512 is used for programming the site specific
data (SSD) and to download it into the EBL512 control unit(s) and/or
1728, 1735 / 1736 & 1826 / 1828 units connected to an Ext. FBP/DU
interface board 1587.
When the units are running (i.e. they are power supplied) and when
required, the TLON network programming (configuration) is done, the
SSD download can start.
The PC has to be connected to the "D" connector J1 in a control unit
(main board 1556). Start Win512. Now you have to be authorised,
58
i.e. you have to log on
In Win512 (menu "Tools" | "Download"), you select the unit(s) to
which the SSD is be downloaded.
the installation) will be automatically saved after the download.

Check All Loop Units

In the Win512 COM loop icon pop-up menu can "Check All Loop
Units" be selected. This function can be used after (or before) the
download of SSD. The function is as follows:
The control unit will find all units that are connected on the COM
loop. The addresses (0-127) will be reported to Win512. For all 33xx
units and some of the other units, the type of unit will also be reported.
All differences compared to the Win512 SSD will be listed in the
Win512 log view and can be saved and/or printed out.
NOTE!
During this check the COM loop will be disconnected
(disabled) and no alarms or faults can be activated. Disconnected
COM loop is indicated by the LED "Disablements" (L8).

Single Control Unit

Start the downloading from Win512. A text message will be shown in
the alphanumeric display in the control unit:
Download in progress......
Block nnnn out of xxxx
When the download is completed the following text message will be
shown:
Download completed successfully.
Control unit will now restart
58
Access code for level 5 shall be entered via the PC (Win512).
59
After the download to a control unit an automatic reset/restart will take
place. A number of faults might then be generated. This will cause "heavy
traffic" on the network, which might affect the SSD download to the other
units.