26.6

Display Statistics for Communication (H5/A6)

The statistics can be used during commissioning, service, etc.
Number of pollings is the number of pollings / "questions" sent out by the Control Unit to
all the units connected on the COM loop.
Parity fault is the received number of parity faults and % (faults in relation to pollings).
Number of bit faults is the received number of bit faults and % (faults in relation to
pollings).
No answer is the received number of answer faults / no answers and % (faults in relation
to pollings).
Bit length fault is the received number of bit length faults and % bit length faults in relation
to the pollings.
The number of Parity faults, number of bit faults, no answer and Bit length faults should be
normally "0" or as close to "0" as possible. If not, there are some communication problems
that have to be investigated. Check the COM loop, connections and the loop units.
All values are set to "0" after restart and/or after re-connection of COM loop (via menu
H8/S1).
Action
Text in display
"Menu"
Scroll to menu H5.
H5 Service
A1 Calibration of supervised output
"↲"
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A6
A6 Display statistics for communication
"↲"
Display statistics for COM-loop:
"↲"
Please wait......
No reply from control unit.....
Number of pollings: nnnnnnn
Parity fault: 000000 00.0%
Number of bits fault: 000000 00.0%
No answer: 000000 00.0%
Bit length fault: 000000 00.0%
"↲" or "ESC"
A6 Display statistics for communication
The information is automatically updated every 5 seconds
0
control unit: 00
141
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Write loop number and
control unit number and
press "↲".
If the control unit is not
existing or doesn't
respond.
Note: The values are
not live updated.
Scroll to another menu
or press "ESC".