Operating Instructions Fire alarm system EBL512 G3, V1.1.x
In the c.i.e. display can up to three fault messages be shown
simultaneously. In the display, down to the left, is
displayed the number of not acknowledged faults.
If a fault has been corrected (serviced) before it has been
acknowledged, the status information is "
above.
Fire alarm presentation has higher priority than the fault
messages, however during fire alarm presentation the faults
can be shown via the menu system, see page 42.
NOTE! Two faults also have their separate information
texts shown close to the soft key area, also during fire
Extinguishing fault
alarm:
Extinguishing wire fault
Faults have to be acknowledged, which is done via menu H6 (see page
126). This menu is a list of all faults in the system:
not corrected / serviced and not acknowledged fault
not corrected / serviced but acknowledged fault
corrected / serviced but not acknowledged fault
If a fault cannot be corrected, it is important to contact service
personnel / engineer immediately.
NOTE!
As a reminder, faults (and disablements) are indicated by a 2-sec. beep
when an open c.i.e. door is being closed.
53
", see
serviced
and
.
(acknowledged)
(serviced)