Panasonic MEW01349 Operating Instructions Manual page 42

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
First alarm: 002-03
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
are activated, no more fire alarms will be shown until one or more of
the first 512 fire alarms are reset.
It is possible to have Selective alarm presentation, i.e. only fire
alarms from selected control units will be presented Set in WinG3.
(Normally all fire alarms will be presented in all control units.)
See also chapter "The information area priority order", page 22. In
accordance with the EN54-2 standard, the following happens in case
of a fire alarm:
 The buzzer in the c.i.e. sounds 0.4 sec. each 0.4
0.4 sec.).
 LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
 Output for routing equipment (Fire brigade tx) and outputs
type "Routing equipment" are activated.
 Outputs for fire alarm are activated.
 In the c.i.e. display, a presentation number (zone/address) is
shown (for the first fire alarm).
 In the c.i.e. display, a user definable text message (alarm
text) is shown (if programmed).
 In the c.i.e. display, is also some additional information
presented.
One alarm point activating fire alarm.
Example; fire alarm zone 002, address 03 (within zone 002):
Zone
002-03
User definable alarm text for 002-03.
Menu
After the presentation number is automatically added
HEAT, MULTI or MCP depending on type of alarm point.
19
In case of Selective alarm presentation only for the selected alarms.
20
Outputs programmed for General fire alarm and outputs programmed for
the activated fire alarm(s).
40
th
sec. (0.4 /
19
20
Alarm number 1 (of 1)
Address
SMOKE
1 zone in alarm
SMOKE,