First alarm: 000-00
15.5.2
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
brigade tx) will be activated. See EBL512 G3 Planning Instructions
for more information regarding the AA function. Acknowledgement
and reset of the AA alarm can be done on an AA unit 1735 / 1736 or
an AA controller 1740. See also chapter "Alert Annunciation", page
50.
Key cabinet alarm
The fire brigade uses a key cabinet to store a key to the building.
One programmable input per c.i.e. can be used to connect a key
cabinet.
Key cabinet opened before a fire alarm
If the key cabinet is opened before a fire alarm (e.g. if somebody
illegally breaks into the key cabinet), a key cabinet alarm will be
activated.
Example; Key cabinet alarm. xx = Control Unit number (00-29):
Alarm from key cabinet control unit XX
Menu
When printer is available the Key cabinet alarm will be printed like a
normal fire alarm (see above).
Key cabinet alarm is reset like a normal fire alarm, see chapter "Fire
alarm reset, page 49.
This alarm will also generate a fault message, see chapter "Key
cabinet alarm reset", page 51. It is indicated by LED "Fault" (L9).
NOTE! The "Fault tx" output(s) will not be activated by this fault.
Key cabinet opened in conjunction with a fire alarm
If a normal fire alarm already is activated in the c.i.e. the fire brigade
personnel can open the key cabinet without activating any key cabinet
alarm or fault.
45
Alarm number 1 (of 1)