Activate Address Setting Mode For Du (H5/A7) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
28.8
Action
"Menu"
"↵ "
Scroll to menu A7
"↵ "
"↵ "
Rev: -
Activate address setting mode for DU
(H5/A7)
This function can be used by commissioning / service engineer to
activate the address setting mode in the following Display Units
connected to the c.i.e.:
 Ext. Presentation unit 1728
 Alert Annunciation units 1735 & 1736
 Ext. FBPs 1826 & 1828
A specific unit or all units connected to one c.i.e. can be activated for
address setting.
NOTE! The units have to be in operation and in quiescent condition,
i.e. the units have to have an address already.
Text in display
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A7 Activate address setting mode for DU
Activate address setting mode for DU:
Control unit: 00, display unit: 00
A7 Activate address setting mode for DU
The address is thereafter edited in the display unit (DU) respectively.
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
All
125
Comments
According to chapter
"Access code for service /
maintenance (H5 and
H8)", see page 116.
Write control unit number,
and the unit's address or
select (press "►") "All"
(i.e. all display units on the
selected control unit).
Scroll to another menu or
press "ESC".