Disable Output (H2/B3) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
25.3
Action
"Menu"
Scroll to menu H2.
"↵ "
Scroll to menu B3.
"↵ "
"↵ "
Depending on the
selected type the
following will be
shown:
"↵ "
Rev: -

Disable output (H2/B3)

All outputs (except outputs type "Alarm device") can be
individually disabled. Disabled output will stay in (or return to) the
normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1 from which it is also
possible to get a print-out.
Text in display
H2 Disable or re-enable
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
B3 Disable output
Disable output type:
Disable 000000 output 0
(press ↵)
Disable CU: 00 S: 0
(press ↵)
Disable CU: 00 R: 0
(press ↵)
Disable control unit: 00 exp. board: 0 output: 0
Disable output type:
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
3361/3364
S
R
Expansion board
3361/3364
S
R
Expansion board
94
Comments
According to chapter
"Access", see page 85.
Select output type.
S=CU voltage output S0-S3.
R=CU relay output R0-R1.
Press "
" to accept.
for the
Write the data
output respectively.
Press "
" to accept.
LED Fault / Disablements
"General disablements"
(L10) will light up.
Disable another output or
press "ESC". Scroll to
another menu or press
"ESC".