Panasonic MEW01349 Operating Instructions Manual page 140

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Power off / Power on
or
after 5 min.
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
FAULT: Restart control unit nn, code xx
address yyyyyyyyyy
yyyy-mm-dd hh:mm
NOTE!
Before the very first safe shut down the Flash ROM is empty. Then
every time safe shut down is performed the valid data will be saved in
the Flash ROM, i.e. any old data will be overwritten.
When the c.i.e. is powered up, the data stored in the Flash ROM will
be used.
WARNING!
If safe shut down is not performed just before a c.i.e. power down,
then by power on the Flash ROM might be empty or the stored data
might be old / not valid.
,
138
After a restart / power on
(see page 81), there will
always be a fault
generated. The code will
be 00 and the address 0.
This fault has to be
acknowledged, see chapter
"FAULT Acknowledge
(H6)", page 126.