"Silence Alarm Devices; Silence Alarm Devices (Inside Switch) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
8
8.1
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

"Silence Alarm devices"

In the control unit front (the FBP part) there is a push button "Silence
alarm devices" (P2).
When the alarm devices are activated (sounding)
"Silence alarm devices" is pressed, the following will happen:
 The activated outputs programmed for sounders (i.e. type
"Alarm devices", will be turned OFF (de-activated)
If the push button "Silence alarm devices" is pressed again, the
sounders will automatically sound again.
In case of a new alarm the sounders will automatically sound again.
In WinG3, the function "Silence Switch Disables Alarm Devices" can
be selected. In this case the button "Silence alarm devices" (P2) will
have the same function as the menu "Disable / re-enable alarm devices
(H2/B8)". See also chapter "Disable / Re-enable alarm devices", page
31.

Silence alarm devices (inside switch)

NOTE! The functions in this chapter are valid for the New Zealand
convention only.
The button "Silence alarm devices" (P2) is called the "inside switch"
and has the following function:
The inside switch toggles between two states.
9
E.g. during Fire alarm or Alert Annunciation alarm.
10
Including Addressable siren 3377 and Addressable sounder base 3379.
28
9
and the push button
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3 v1.1.x

Table of Contents