Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Key cabinet alarm reset

A key cabinet alarm has to be reset like the normal fire alarms.
After reset a fault message is shown in the display to inform the user
that the key cabinet has been opened.
FAULT: Key cabinet, control unit xx
yyyy-mm-dd hh:mm
NOTE! The date is for the Australian, New Zealand, Russian and
Ukrainian languages shown as dd-mm-yyyy.
xx = control unit number (00-29).
If the key cabinet is closed again, the "status" information is changed
to: "serviced"
This key cabinet fault message is to be acknowledged the same way as
"normal" faults, see chapter "Fault acknowledge", page 69.
When the key cabinet fault is acknowledged, the LED Fault /
Disablements "General fault" (L9) will be turned off (i.e. if the key
cabinet is closed and if there are no other faults in the system).

Co-incidence alarm

A Co-incidence alarm can be manually reset with the "Reset" button
(P3) on the c.i.e. front or automatically reset after 5 minutes (i.e. if the
alarm point / zone is no longer in alarm status). See also chapter "Co-
incidence alarm (2-address / -zone dependence)", page 46.
Alarm Acknowledgement Facility (AAF)
reset
NOTE! The AAF function is used in conjunction with an AAF
Control, which today is available on the Australian market only.
The
indication
Acknowledgement Period (10-60 sec.) and the Investigation Period
(0-3 min.) respectively, will automatically disappear when:
 the AA process ends because no detector in the AAF zone is
over the fire alarm level.
 the AA process ends up in a fire alarm, which has higher
priority. (Regarding Fire alarm reset, see above.)

Quiet alarm reset

Quiet alarms are non-latching, i.e. they will be automatically reset
when the alarm point / zone is no longer above alarm level. Outputs
activated by quiet alarm will be de-activated. (In some cases after a
programmable delay time.)