Panasonic MEW01349 Operating Instructions Manual page 80

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Progress bar
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
2. Set the Main board 5010 in "boot" mode, i.e. hold the "Boot"
button (SW2) down and push the "RESET" button (SW1)
momentarily until the Main board 5010 is in "boot" mode,
indicated by the Main board LED "D24" turned off.
3. Start the download, i.e. click "Start".
LED "Operation" (L5) will be turned off.
LED Fault / Disablements "General fault" (L9) is turned on,
indicating that EBL512 G3 is in the "boot" mode.
LED "System fault" (L7) will be turned on.
If it is an EBL512 G3 type 5000 (i.e. with front), another dialog
box opens,
Set the MMI board 5011 in "boot" mode, i.e. hold the "BOOT"
button (SW2) down and push the "RESET" button (SW1)
momentarily until the MMI board 5011 is in "boot" mode,
indicated by the MMI board LED "D18" turned off.
4. Click "OK".
The download status is indicated by the progress bar.
5. When the progress bar has gone from "red to green" the download
is completed and the following dialog box opens:
78

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3 v1.1.x

Table of Contents