Clear Weekly Average (H8/S4) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
31.5
Action
"Menu"
"↵ "
Scroll to menu S4.
"↲ "
"ESC"
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Clear weekly average (H8/S4)

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
cleared and set to the default value otherwise the new / clean sensor
will inherit the old sensor's value. It is possible to clear the week
average sensor value for each sensor individually via this menu.
NOTE! First replace the sensor and then clear the week average
value as soon as possible. Authorised service personnel only, must
do this. Used incorrectly it can cause nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated
within one hour, then each week.
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
S4 Clear weekly average
Clear weekly average zone: 000 address: 00
(press ↵)
S4 Clear weekly average
134
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
Write the wanted zone and
"↲ "
address and press
.
Continue like above or
scroll to another menu or
press "ESC".