LED indicator
L7
System fault (yellow)
L8
Test mode (yellow)
Fault / Disablements
L9
General fault (yellow)
L10
General disablements
(yellow)
L11
Alarm devices (yellow)
L12
Fire brigade tx (yellow)
Routing equipment
L13
Fault tx activated (yellow)
L14
Fire brigade tx delay
(yellow)
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
LED indicators on the Control Panel (CP)
Indicating
EBL512 G3 is not running because of S/W, CPU or
memory fault.
One or more zones are in "test mode", see page 87 and
127.
Fault(s) in the system, i.e. not acknowledged fault(s)
and/or not corrected fault(s). See also page 126.
Disablement(s) in the system. Also valid for "Single
with automatic disablement", see page 50.
Steady / cont.: Output(s) type "Alarm device" are
disabled.
Blinking: One or more supervised outputs type
"Alarm device" have generated fault(s).
This is also valid when the c.i.e. has no "contact" with
a unit with such an output, e.g. 3377, 3379, 3364, etc.
Steady / cont.: Output(s) for "Routing equipment"
disabled via menu (H2/B3 or B9) or via open door.
Blinking: Routing equipment power supply output
one or more supervised outputs (of type "Routing
equipment" have generated fault(s). This is also valid
when the c.i.e. has no "contact" with a unit with such
an output, e.g. 3361, etc.
One or more not acknowledged faults.
condition" for fault tx (routing equipment) is activated.
Test of routing equipment in progress (see menu H1).
Sensitive fault detection mode (see menu H5/A2) is on.
The Alert Annunciation function is enabled, i.e. time
channel controlling this function is "on". The AA
function is described in the EBL512 G3 Planning
Instructions, chapter "Alert Annunciation". LED
"L14" will be "on" if the AA function is enabled for at
least one alarm point / zone. Normally is only one
time channel used for this function but two or more
channels can be used. The AA function can, as an
alternative, be continuously "on".
3
Main board 5010 term. block "J3:3-4", fuse F8 (T500mA L 250 V – TR5).
4
See also chapter "Fault acknowledge", page 70.
19
3
or
4
Output "Fault