Operating Instructions Fire alarm system EBL512 G3, V1.1.x
supervised input in the EBL512 G3 system, in control unit no. xx.
Check the input connections as well. (Normally used for German
routing equipment connected to an expansion board 4583 input 0.)
FAULT: FB Silence switch,
control unit xx
Only valid in the New Zealand convention.
New Zealand FB Silence switch ("outside switch") is turned on, in
control unit no. xx, i.e. from not activated to activated state.
FAULT: Fire brigade panel xx,
control unit xx
FBP=1826 / 1828 (Ext. Fire Brigade Panel)
The ext. FBP xx, connected to control unit no. xx, is programmed as
another type in the SSD or a fault in the unit.
FAULT: Fuse on COM-loop x,
control unit xx
Blown fuse F15 (Loop 0), F16 (Loop 1), F17 (Loop 2) or F14 (Loop
3) on the main board 5010, in control unit no. xx. Fuse T1.6A L 250V
(TR5). NOTE! The fuse shall not be replaced. The main board 5010
shall be replaced, since more components are broken as well.
FAULT: Interlocking input AAA/PP
An interlocking input is not activated within the time set for fault
activation (5-255 seconds). The time is counted from the activation of
the output in the interlocking combination, area AAA / point PP.
FAULT: Internal short circuit, COM-loop x
control unit xx
Short-circuit on the connection (ribbon cable) to or between the
expansion boards (458x) in the control unit xx (EBL512 G3).
FAULT: Key cabinet, control unit xx
The key cabinet has been opened without a prior fire alarm (i.e. if
somebody has opened the key cabinet illegally).
or
The key cabinet has not been closed within 5 minutes after reset of all