Led Indicators And Push Buttons - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
5
LED indicator
L1
Fire (5 red)
L2
Extinguishing (red)
L3
Ventilation (yellow)
L4
Fire brigade tx (red)
L5
Operation (green)
L6
Alarms queued (2 red)
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

LED indicators and push buttons

LEDs and push buttons can vary according to type and configuration
(convention / country / language).
See also Figure 2, page 16.
LED indicators on the Fire Brigade Panel (FBP)
Indicating
Fire alarms (see below)
Co-incidence alarm
Pre-warning
Quiet alarm (normally Australia only)
Alarm Acknowledgement Facility (AAF) alarm (Australia
only)
See also chapter "Alarm types", page 38.
Output(s) for extinguishing equipment activated. (Or a
programmable input type "Extinguishing" is activated.)
Output(s) for fire/smoke ventilation equipment activated. (Or
a programmable input type "Ventilation" is activated.)
Output "Fire alarm" for fire brigade tx (routing equipment)
and/or corresponding programmable output(s) of type
"Routing equipment") is/are activated. (Or a programmable
input type "Activated routing equipment" is activated.)
Test of routing equipment in progress (see menu H1).
The c.i.e. is powered via the rectifier and/or the battery.
More than one unit / zone have activated fire alarm. Use
push button "Alarms queued" (P8) to scroll amongst the
alarm points or soft key "Next zone" (P5) to scroll amongst
the zones.
NOTE! Fire alarms are:
Fire alarm (incl. test mode alarm)
Heavy smoke/heat alarm
Alert Annunciation (AA) alarm
Key cabinet alarm
Acknowledged alarm (New Zealand only)
Isolated alarm (New Zealand only)
17