Operating Instructions Fire alarm system EBL512, V2.7.x
input in control unit xx.
FAULT: Fan xx, control unit xx
The LED "Fault" is lit on a fan control module connected to control
unit xx. Fan no. xx has been activated but the corresponding I/O unit
3361 input has not been activated within 30 seconds.
 Check the fan and the cables / connections.
FAULT: FB Silence switch active
Only valid in the New Zealand convention.
New Zealand FB Silence switch ("outside switch") is turned ON, i.e.
from not activated to activated state.
FAULT: FBP xx, 1587-board x, CU xx
FBP=1826 / 1828
The unit is programmed as another type of unit than the SSD says or
fault in the unit.
FAULT: FBP xx, CU xx
FBP=1826 / 1828
The unit is programmed as another type of unit than the SSD says or
fault in the unit.
FAULT: Fuse, 1580 8 zones board x, CU xx
(DET8=1580, 8 zones expansion board)
Check for blown fuse on the 1580 board.
FAULT: Fuse, 1582 FBP board x, CU xx
(External Fire Brigade Panel interface board 1582)
Check for blown fuses on the 1582 board.
FAULT: Fuse, 1584 Autron. board x, CU xx
(BS4=1584 Autronica interface board)
Blown fuse on the 1584 board. The fuse is not replaceable. The
65