Operating Instructions Fire alarm system EBL512, V2.7.x
Zones in test mode: 001, 002, 003, 004
NOTE! See chapter "Alphanumeric display (LCD) in
EBL512", page 21 regarding priority order.
Zone in TEST MODE:
001 002 003 004
Perform ZONE TEST
NOTE! During the test, the following information will be shown in
all other c.i.e. displays:
Zones in test mode: 001, 002, 003, 004
(In DBI (Danish) convention, only one zone.)
NOTE_2! If an alarm point (e.g. a manual call point) is in alarm state
when the test mode is ended, there will not be a fire alarm activated.
Instead the alarm point will be disabled and has to be re-enabled again
via menu H2/B5.
When the "Fire door closing" function is used, the fire door will be
closed when the detectors controlling the door are tested via the test
mode.
End test:
ACCEPT
ACCEPT? H7
140
You are no longer in menu
H7 but still in test mode.
Press "A" to end the test
mode.
The LED "Test mode" is
turned OFF.
If more zones are to be
tested, continue as above.
If not, scroll or press
"Return" to log off.