Operating Instructions Fire alarm system EBL512, V2.7.x

Disable interlocking output (H9/C4)

Interlocking outputs (Type = Interlocking) can be disabled via this
menu but not via menu H2/B3.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. If "000/00" is entered, all interlocking outputs will
be disabled at the same time.
Up to 200 interlocking outputs can be disabled.
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
The LED "Disablements" (L8) is also indicating one or more disabled
interlocking outputs.
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Disable interlocking output
Disable interlocking output
area 000 point 00
Disable interlocking output
area 001 point 01
Disable interlocking output
ACCEPT? H9
ACCEPT? C1
ACCEPT? C4
ACCEPT?
ACCEPT?
ACCEPT? C4
158
Comments
According to chapter
"Access", see page 92.
Press "A" to accept and/or
"Return" to menu C3.
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.