Operating Instructions Fire alarm system EBL512, V2.7.x

Disable zone / address (H2/B2)

Addressable alarm points (also addressable manual call points),
connected to the COM loop, can be individually disabled.
Disabled alarm points, zone / addresses, are listed in menu H4/U1
from which it is also possible to get a print-out.
Regarding disabled analog smoke detector: The sensor values will not
be saved, i.e. only the values saved before and after the disablement
will be used when calculating the week average sensor value.
Disabled alarm points, zone / addresses, have to be re-enabled via
menu H4/B2.
Text in display
Disable or re-enable
Disable zone
Disable zone / address
Disable zone: 000 Address: 00
Disable zone: 001 Address: 01
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM
(Default is current time + 3 hours)
Disable zone: 000 Address: 00
ACCEPT? H2
ACCEPT? B1
ACCEPT? B2
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
98
Comments
According to chapter
"Access", see page 92.
Press "A" to accept.
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept. LED
"Disablements" (L8) will
light up.
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B2.
Scroll or press "Return"
to menu H2. Scroll or
press "Return" to log off.