Operating Instructions Fire alarm system EBL512, V2.7.x
Fire alarm presentation in the EBL512 display
1
2
3
4
5
6
7
8
9
0
1
2
3
A
A: Field for the first alarm point or zone in alarm.
By scrolling each alarm will be shown in this field.
B: Field for the most recent (last) zone in alarm.
C: Field for total number of zones in alarm.
D: Field for alarm text. (User definable.)
Only one alarm point activated in a zone is presented as zone-address
(POINT: or LAST:)
Two or more alarm points activated in a zone is presented as zone
only (ZONE: or LAST:).
One alarm point
POINT: 123-45
User definable text message for 123-45
More than one alarm point in a zone
One conventional zone (zone line input)
ZONE: 123
User definable text message for zone 123
More than one zone
ZONE: 234
User definable text message for zone 234
Only one alarm point in each zone
POINT: 123-45
User definable text message for 123-45
LAST = The most recent zone-address that has activated fire alarm.
No. = The total number of zones where fire alarm is activated.
User definable text message (alarm text) For an alarm point it is the
individual (free) text for the alarm point (if programmed) or the
default control unit text (if programmed).
47
Plus Alert Annunciation and Ext. Presentation units. In the "old" ext.
FBPs 2425, 2426 and 2428 only the ten first fire alarms will be displayed.
48
In New Zealand convention the presentation is different and described in
separate documents.
49
More than one alarm point in the same zone: If no user definable text
message is programmed, the text "Many alarms in zone" will be shown.
42
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
or
LAST: 567
LAST: 789-01
48
:
B
1
2
3
4
5
6
7
8
9
0
C
D
No.:001
No.:001
49
No.:002
No.:003