Sensor Values (H4/U3) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
27.3
"Access"
Scroll to menu H4.
"A"
Scroll to menu U3.
"A"
E.g: "01-01"
"A"
Depending on
the type, the
""
following will
be shown
""
(examples):
"A"
""
"A"
""
""
Rev: 3

Sensor values (H4/U3)

The very first week average sensor value is calculated within 2
minutes after SSD download & restart. During these 2 minutes, fire
alarm from analog smoke detectors are suppressed and the sensor
value "000" will be shown.
The "Performance factor" and "Min. / Max." values are updated each
night (00:00), i.e. the values shown are from the previous day.
Text in display
Present system status on display
Disablement
Sensor values
Start Sensor : 00-00
Type 4301:
Sensor: 01-01 (technical address 001)
Momentary: XX.X%/m
Sensor: 01-01
Perf Factor: X.XX%/m
Sensor: 01-01
Current algorithm: nnnnnn
Type 3308/3309:
Sensor: 01-02 (technical address 002)
Momentary: XX°C
Sensor: 01-02
Current algorithm: nnnnnn
Type 4300:
Sensor: 01-03 (technical address 003)
Momentary: XX.X%/m
Sensor: 01-03
Perf Factor: X.XX%/m
Sensor: 01-03
Current algorithm: nnnnnn
EBL128 Operating Instructions V1.1.x
ACCEPT? H4
ACCEPT?
ACCEPT?
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
Min: XX°C
Max: XX°C
Weekly: XX.X%/m
Min: XX.X%/m
Max: XX.X%/m
97
Comments
According to chapter
"Access", see page 78.
U1
Press "A" to accept.
U3
Write the presentation
number and/or press "A"
to accept.
This is a list in which
you can scroll or use
""
to see the next
information window for
the selected sensor.
Press "Return" back to
"Start Sensor...".
Scroll or write a new
presentation number or
press "Return" to menu
U3.
NOTE!
XX.X%/m = XX.X %
obscuration per meter".
Perf. Factor: see below
this table.
nnnnnn = algorithm short
name, see separate table,
page 98.