Disable All Control, Ventilation, Exting Or Interlocking Outputs; (B4) - Panasonic EBL128 User Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
5.4
Disable all control, ventilation, exting or
interlocking outputs (B4)
Not available for users with access level / type "Information only".
Outputs programmed as type Control (general), type Fire ventilation,
type Extinguishing system and type Interlocking can for the type
respectively be collectively disabled (all at the same time) via menu
B4. Disabled output will stay in (or return to) the normal condition
for the output respectively.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "2") to menu H2.
H2 Disable or re-enable
Press "A" to sub menu B1.
B1 Disable zone
Scroll (or press "4") to menu B4.
B4 Disable all control, ventilation, exting
or interlocking outputs
Press "A".
Use the keypad to select output type:
0=Outputs type Control (not control neutral).
1=Outputs type Ventilation
2=Outputs type Extinguishing
3=Output type Interlocking.
Press "A".
Disabled (or not disabled) output type information is shown. Press
"A". When required, disable more output types or press "Return" to
menu B4.
Scroll to another menu or press "Return" to menu H2. Scroll to
another menu or leave the menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual
13