Table 18 Other units current consumption

Other units
Routing equipment (Fire brigade TX / Fault TX)
External Presentation unit 1728
Alert Annunciation unit 1736
Alarm devices (sounders, etc.)
Occupant Warning System (OWS) 60W
Magnetic door holder
As more loop devices are added, they are summarised in the "Summary of loop units"
providing information for total quiescent and maximum consumption in the "Properties for
NMAST loop" dialog box. See Figure 57 below for steps to access the information from
EBLWin under their respective loops.

Figure 57 Access to COM loop units current consumption

The current consumption of FT1020G3 from the power supply and the charging current for
the battery with battery temperature can be displayed via menu H5/A4.
An approximate value of individual COM loop is also displayed via menu H5/A5.
180
Quiescent and alarm current must be added correctly for each brigade unit e.g. Romtec, Tyco ASE, etc. Separate power supply
and batteries may be required.
181
OWS with higher wattage e.g. 120W or 250W requires separate power supply and battery backup.
Normal state
(quiescent) (mA)
See foot note
26@24 V / 48@12 V
26@24 V / 48@12 V
0
181
118
Approximately 80
176
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Alarm state
(activated) (mA)
180
180
See foot note
49@24 V / 88@12 V
42@24 V / 79@12 V
Sounder type current
3100