Parameters For Smoke Algorithms; Figure 53 Alarm Algorithms Dialog Box; Figure 54 Smoke / Heat Algorithms Example - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

Technical/Programming Manual
FT1020G3 Rev 2.2.1

Figure 53 Alarm Algorithms Dialog Box

Figure 53
To open the Alarm Algorithms Dialog Box as in
, click System | Alarm Algorithms
from the EBLWin menu.
All the different algorithms for the different detector types are shown in the tree view to the
left. Click "+" to expand and "-" collapse the tree view.
Select one algorithm and click "Edit" and a dialog box displays depending on the selected
algorithm:

Figure 54 Smoke / heat algorithms example

Figure 54 shows Smoke algorithm N-15 for 4301 / 4401, Heat algorithm Class A1 for 3308
and Combined Decision algorithm Dec for 4300 / 4400 respectively. All in NORMAL mode.
Detector: abbreviations and Type number (e.g. OPT 4401 = Analogue photoelectric
(optical) smoke detector, AHD 3308 = Analogue heat detector and AMD 4400 = Analogue
Multi Detector).
Name: Name of the algorithm (e.g. N-15, Class A1 & Decision). Normally not changed.
Abbreviation: The algorithm abbreviation (< six characters) as shown in the FT1020G3
display, menu H4/U4 (e.g. N-15, A1 & Des). Normally not changed.
22.3.3.1

Parameters for smoke algorithms

Valid for the detectors 4300 / 4400 and 4301 / 4401. All in NORMAL mode.
154

Advertisement

Table of Contents
loading

Table of Contents