26. Output is activated only if the first alarm is an alarm in the specified Zone in the
specified Zone Group.
27. Pre-warning, Output is activated when any of the alarm points in the specified Zone
Group exceeds the pre-warning level. See also 4 above regarding the quantity. For
information refer to the FT128 Operation Manual.
28. Fire alarm, Output is activated when any of the alarm points in the specified Zone
Group is in alarm. See also 4 above regarding the quantity. For information refer
to the FT128 Operation Manual.
29. Heavy smoke / heat alarm, Output is activated when any of the alarm points in the
specified Zone Group exceeds the heavy smoke / heat alarm level. See also 4.
Above regarding the quantity. For information refer to the FT128 Operation
Manual.
Interlocking
30. Output activated when one or more interlocking inputs, in the specified interlocking
area, are activated.
31. Output activated when the interlocking input, in the specified interlocking
area/point, is activated.
32. Output activated when any interlocking inputs is activated.
33. Output activated when interlocking inputs, in the specified range, are activated
(from interlocking area no./point to interlocking area no./point). See also 4. above
regarding "Quantity".
Disablement
34. Output activated when any Routing equipment output (Fire brigade TX) is
disabled
35. Output activated when the specified zone is disabled
36. Output activated when the specified alarm point (zone- address) is disabled
37. Output activated when any alarm point (zone/address) or zone is disabled
38. The control expression is true (output activated) when all control outputs of the
types Control, Fire ventilation and Extinguishing are disabled via menu
H2/B3
39. The control expression is true (output activated) when all control outputs of type
Alarm device in all control units are disabled via menu H2/B4
be type Alarm devices
40. The control expression is true (output activated) when all control outputs of the
types Control, Fire ventilation and Extinguishing in the specified control
unit are disabled via menu H2/B3
41. The control expression is true (output activated) when all control outputs of type
Alarm device in the specified control unit are disabled via menu H2/B4). This
out put has to be type Al arm dev i ce s.
42. The control expression is true (output activated) when any disablement exists
in the system
98
Indicated by LED Fault / Disablements "Fire brigade TX".
99
Indicated by LED Fault /Disablements "General Disablements".
100
Indicated by LED Fault / Disablements "Alarm devices".
98
.
. This output has to be type Control – neutral.
99
99
.
90
Technical/Programming Manual
99
.
. This output has to be type Control – neutral.
99
FT1020G3 Rev 2.2.1
99
.
99
.
100
. This output must